What Size Cable Do I Need? (Inverter, Battery & Generator Cord Calculator)

Pick a copper wire gauge (AWG) for a battery bank, inverter, backup power circuit or generator extension cord. The calculator checks two things, how much current the wire can safely carry and how much voltage you lose along the run, and keeps the larger size. Choose your country first: the US and Canada use different codes.

Recommended copper wire
–
–
Design current
–
–
Voltage drop at this size
–
–

Safety first. This is a planning estimate, not a substitute for your inverter or battery manual, your local electrical code or a licensed electrician. Always put a fuse or breaker close to the battery positive terminal. A battery bank can deliver thousands of amps into a short circuit. Wiring that connects a generator or inverter to house circuits needs a transfer switch or interlock, so you never backfeed the grid.

How the calculator works

  1. Current: amps = watts ÷ volts, then ÷ 0.9 for inverter losses if you ticked that box.
  2. Continuous loads: in the US (NEC), conductors and breakers for continuous loads (3 hours or more) are sized at 125% of the load.
  3. Ampacity: each size’s maximum current comes from NEC Table 310.16 (conduit or cable) or Table 310.17 (single conductors in free air), copper, 30 °C ambient. Sizes 14, 12 and 10 AWG are capped at 15, 20 and 30 A, the overcurrent limits for small wire.
  4. Voltage drop: drop = 2 × length × amps × resistance, using copper resistance at 75 °C (NEC Chapter 9, Table 8).
  5. Fuse: the smallest standard size that covers the load. If that fuse is larger than the wire can carry, the calculator moves up one wire size.

Solid or stranded? Solid wire is fine for fixed house wiring inside walls, usually 10 AWG and smaller. Use fine-stranded cable for anything that moves or vibrates, and for most battery and inverter connections. Finish stranded ends with crimped lugs or ferrules, and never tin them with solder before clamping.

Hot spaces, bundled cables or more than three current-carrying wires in one conduit all lower a wire’s ampacity. In those cases, go one size up or apply the correction factors in NEC 310.15.

Sources: NEC (NFPA 70) Tables 310.16 & 310.17 and Chapter 9 Table 8, as summarised in Omni Cable’s NEC ampacity data. Where your equipment manual lists a cable size and fuse, follow the manual.

Frequently asked questions

What gauge wire do I need for a 2000 W inverter?

On a 12 V battery, a 2000 W inverter draws about 185 A at full output (including roughly 10% inverter losses). With the NEC’s 125% margin for continuous loads, that’s about 231 A, which points to 2/0 AWG copper for a short run of single cables in free air, with a 250 A fuse. On a 24 V battery, the current halves and about 4 AWG is enough. If your inverter manual lists a cable size and fuse, follow the manual.

What size extension cord do I need for my generator?

Match the cord to the outlet you’ll use: 12 AWG for a 20 A outlet, 10 AWG for a 30 A outlet (10/4 for an L14-30 twist-lock), and 6 AWG for a 50 A outlet. Long cords at full load can need one size heavier to keep the voltage drop down; switch the calculator to “Generator extension cord” to check yours. Use an outdoor-rated cord, and keep the generator at least 20 feet from the house.

Can I use 12 AWG wire on a 20 amp breaker?

Yes. 12 AWG copper is the standard size for 20 A circuits in both the US and Canada. 14 AWG copper is limited to a 15 A breaker, and 10 AWG to 30 A.

Should battery cables be solid or stranded?

Stranded, ideally fine-stranded battery or welding cable. Battery and inverter cables flex and vibrate, and solid wire can crack and won’t seat properly in a crimped lug. Solid wire belongs in fixed house wiring inside walls.

Why do lithium batteries need a Class T fuse?

LiFePO4 batteries have very low internal resistance, so a short circuit can push a huge current. A fuse has to be able to break that current safely. Class T fuses are rated to interrupt 20,000 A, far more than typical ANL fuses, which is why many inverter and battery makers specify them for lithium banks.

Are the US and Canadian wire tables different?

For copper wire from 14 AWG to 4/0, the ampacity tables in the NEC (310.16 and 310.17) and the Canadian Electrical Code (Tables 1 and 2) list the same values. The rules around them differ: Canada handles continuous loads under Rule 8-104 and requires CSA-certified cable. Pick your country at the top of the calculator.

Planning battery backup for the next winter outage? The Winter Battery & Power Outage Guide shows you how to test your batteries in minutes, keep them alive through the cold, and get through the first hours of an outage safely, generators included. 46 pages plus a printable one-page Outage Card. $12.99, instant PDF download. See what’s inside the guide →